| General |
| Applied Specification |
- Korean Standard(KS)
- Korea Electronic Manufacturing Coop (KEMC-1111)
- Japanese Electronic Manufacturing(JEM-1354)
- German Industrial Standards (DIN-6720) |
| Operating Condition |
- Surrounding temp : MIn. -15~Max. 40
- Altitude : under 1,000m above sea level
- Humidity : Indoors (Machine room temp 5~40¡É) |
| Rated Output |
- Generator output standard date
- Stand By : 1 out of 12 hours of continuous use is possible, used when average output is under 90% of stand by output
- Prime : As the maximum continuous output, 1 out of 12 hours can be operated with a 10% overload(DIN 6270B) |
| Lubrication Oil |
- RIMULA-X 15W/40, Multigrade (Maker:SHELL) or equivalent |
| Fuel Oil |
- Standard : ASTM NO.2 DIESEL OIL
- Recommended : Domestically distributed Low-Sulfur Diesel |
| Painting Color |
- Diesel Generator and accessories : Engine original color, Silencer is
- Heat proof (Silver or black)
- Control Panel : MUNSELL No. 5y 7/1 |
|
| Diesel Engine |
| Engine Type (60Hz/50Hz) |
- High-speed engine : 1800/1500RPM |
| Engine Maker |
- Doosan / MITSBUISH/ CUMMINS / CATERPILLAR / HYUNDAI / VOLVO / MTU / PERKINS / etc |
|
| Diesel Engine |
| Rated voltage |
220 V, 380 V,440 V,3300 V,6600 V |
| Revolution |
800/1500 |
| Frequency |
60Hz, 50Hz |
| Power Factor |
0.8 (Land-level) |
| Wire Connection |
WYE (Y) |
| Exitation System |
Self Exciting Brushless Type |
| Insulation Class |
F (H) |
| Voltage adjust range |
¡¾5% |
| Cooling |
Automatic cooling by Fan, Water Cooling |
| Voltage Variation |
¡¾2.5% |
|
| Operation Control Panel Capacity(Control Panel)
|
| Structure |
- Separate form, front door t 3.2 mm, back door t 2.3 mm, frame t. 2.3mm thick rolled steel type 1 is used.
- The front side has the main circuit breaker, push button, lamp, switch, and gauges on it.
- Both front and back doors are in the Hinge Type, and facing the door, the Handle is on the left, the hinge is on the right.
- In the operation panel, a ground line(Cu, t5¡¿25) is installed.
- Control circuit is on principle, ducked circuit, and when inevitable, it is done in bundles.
- It it for indoor use, and protection rate is IP40.
- The conductor for main power consists of the Bus Bar, maintaining an adequate distance, and exposed parts are plated with tin. |
| Rated Voltage |
220V, 380V, 440V, 3300V, 6600V |
| Power and load connection |
- Power Income : Connect cable under the Panel
- Load Output : Connect cable under the Panel |
Wiring
¡ØUses 600V,and the wiring capacity is as the following |
- Gauge flow transformer¡¯s 2nd circuit: 3.5mm©÷Green
- Gauge voltage translator¡¯s 2nd circuit: 2.0mm©÷Red
- Control Wiring: Yellow
- Ground Wiring : 3.5mm©÷Yellow+Green
- Power Cable Color : Black |
| Name Plate |
On white plastic, black Gothic letters(English and Arabic Numbers) are printed, the size of name plates are as the company¡¯s standards, and are fixed by a Sealer. |
| Wire Maker |
On each end of wires, white vinyl tubes with black letters are fit to make it convenient to distinguish. |
| Annunciator |
All annunciators are set in a wide angle, and all annunciators excluding frequency and voltage have the accuracy of ¡¾1.5%. (Hz : ¡¾10%, PF: ¡¾5.0%) |
| Power to be prepared by customer |
- Jacket Water Heater Controlling power : AC 220V, 1Phase Etc
- Main Circuit Breaker ACB or VCB controlling power : DC 110 V
- When the main circuit is MCCB, MCCB controlling power : DC 24V(No need when electric starting type) |