Power ProductsDiesel Gensets
General Specification  
 
General
Applied Specification - Korean Standard(KS)
- Korea Electronic Manufacturing Coop (KEMC-1111)
- Japanese Electronic Manufacturing(JEM-1354)
- German Industrial Standards (DIN-6720)
Operating Condition - Surrounding temp : MIn. -15~Max. 40
- Altitude : under 1,000m above sea level
- Humidity : Indoors (Machine room temp 5~40¡É)
Rated Output - Generator output standard date
- Stand By : 1 out of 12 hours of continuous use is possible, used when average output is under 90% of stand by output
- Prime : As the maximum continuous output, 1 out of 12 hours can be operated with a 10% overload(DIN 6270B)
Lubrication Oil - RIMULA-X 15W/40, Multigrade (Maker:SHELL) or equivalent
Fuel Oil - Standard : ASTM NO.2 DIESEL OIL
- Recommended : Domestically distributed Low-Sulfur Diesel
Painting Color - Diesel Generator and accessories : Engine original color, Silencer is
- Heat proof (Silver or black)
- Control Panel : MUNSELL No. 5y 7/1
Diesel Engine
Engine Type (60Hz/50Hz) - High-speed engine : 1800/1500RPM
Engine Maker - Doosan / MITSBUISH/ CUMMINS / CATERPILLAR / HYUNDAI / VOLVO / MTU / PERKINS / etc
Diesel Engine
Rated voltage 220 V, 380 V,440 V,3300 V,6600 V
Revolution 800/1500
Frequency 60Hz, 50Hz
Power Factor 0.8 (Land-level)
Wire Connection WYE (Y)
Exitation System Self Exciting Brushless Type
Insulation Class F (H)
Voltage adjust range ¡¾5%
Cooling Automatic cooling by Fan, Water Cooling
Voltage Variation ¡¾2.5%
Operation Control Panel Capacity(Control Panel)
Structure - Separate form, front door t 3.2 mm, back door t 2.3 mm, frame t. 2.3mm thick rolled steel type 1 is used.
- The front side has the main circuit breaker, push button, lamp, switch, and gauges on it.
- Both front and back doors are in the Hinge Type, and facing the door, the Handle is on the left, the hinge is on the right.
- In the operation panel, a ground line(Cu, t5¡¿25) is installed.
- Control circuit is on principle, ducked circuit, and when inevitable, it is done in bundles.
- It it for indoor use, and protection rate is IP40.
- The conductor for main power consists of the Bus Bar, maintaining an adequate distance, and exposed parts are plated with tin.
Rated Voltage 220V, 380V, 440V, 3300V, 6600V
Power and load connection - Power Income : Connect cable under the Panel
- Load Output : Connect cable under the Panel
Wiring
¡ØUses 600V,and the wiring capacity is as the following
- Gauge flow transformer¡¯s 2nd circuit: 3.5mm©÷Green
- Gauge voltage translator¡¯s 2nd circuit: 2.0mm©÷Red
- Control Wiring: Yellow
- Ground Wiring : 3.5mm©÷Yellow+Green
- Power Cable Color : Black
Name Plate On white plastic, black Gothic letters(English and Arabic Numbers) are printed, the size of name plates are as the company¡¯s standards, and are fixed by a Sealer.
Wire Maker On each end of wires, white vinyl tubes with black letters are fit to make it convenient to distinguish.
Annunciator All annunciators are set in a wide angle, and all annunciators excluding frequency and voltage have the accuracy of ¡¾1.5%. (Hz : ¡¾10%, PF: ¡¾5.0%)
Power to be prepared by customer - Jacket Water Heater Controlling power : AC 220V, 1Phase Etc
- Main Circuit Breaker ACB or VCB controlling power : DC 110 V
- When the main circuit is MCCB, MCCB controlling power : DC 24V(No need when electric starting type)